18
FCL
Constant dosing pump withlevel alarm.
Aredledindicatesthattheproduct’stankisempty.Duringthisconditionthepumpdoesnotdose.The
pumphasflowcontrol(frontpanelknobmaybesetfrom0%to100%ofpumpnominalcapacity).Flow
controliselectronicallysetanditoperatesonpumpinjectionsnumber.Toavoidlinearityproblemdo
notsettheknobofpumpflowbetween0%and10%.
FCL has a divider (x- 0,1) to reduce by ten times the pump capacity by dividing the pump stroke
speed.
Howtoenable“dividermode”:
-setthepumpintoSTANDBY*mode;
-keepingpressedtheon/offbutton,wait3flashesfromthestatusled.Thepumpwillstartthedosing
activitywiththestrokespeedreducedtentimesthanthevaluesetonstrokelenghtknob.
Todisablethe“dividermode”,powerOFFthepump.Keepingpressedtheon/offbutton,wait3flashes
ofthestatusled.
STATUSLED
Theledonthefrontalpanelshowsthepump’soperatingstatusthroughfourflashing:
levelalarm
strokespeedknob
statusled
on/offbutton
8. Models
LEDACTIVITY
PUMP’SSTATUS
Itflashes3timespersecond
thepumpispoweredwithapowersupplylowerthanthelabel
Itflashes2timespersecond thepumpispoweredwithapowersupplyhigherthanthelabel
Itflashes1timepersecond
thepumpisinpause(OFF)anditispowered(STANDBY*mode)
ledON,itswitchesoff1timeper
second
thepumpisactiveandfunctioning(ON)
ledON,it switches off 1time
every4seconds
thepumpisworkingintoDIVIDEmode