24
FTE
Timered/constantdosingpump.
Settingtheswitchontheconstant position,thepumphasflowcontrol(frontpanelknobmaybeset
from0%to100%ofpumpnominalcapacity).Flowcontroliselectronicallysetanditoperatesonpump
injectionsnumber.Toavoidlinearityproblemdonotsettheknobofpumpflowbetween0%and10%.
Settingtheswitchontimered ,thepumpstartsworkingwhenanexternalpulseisprovided.Working
activetimeforeachexternalpulseissetontheadjustmentknobintherangebetween0and60seconds
(differenttimeareavailableupondemand).
Thecapacitycanbealsochangedadjustingthestrokeperminute,operatingthe%markedknob,at
thesametime.
Thedoubleparameteradjustment (strokes and time) allowstheuse of this pump inhighcapacity
systems,wherethepulsesarenotenoughtodriveaPVtypepump.
TEpumpisprovidedofacoaxialcable(RG58)withBNCplugtoconnectthecommandsignal.
Usefollowingformulatoevaluatetheknobadjustment:
3600
——————————=sec.
imp/h
imp/h-watermeteroutputpulseperhour
sec-timeinsecondstobesetontimeknob
Maximumtagcapacitycanbedecreased10or100timesinthe“F”and“FA”pumpsusingthe1/10/100
switch(whereavailable).Inthatcasethe%markedknobwillworkonthemaximumsetcapacity.
8. Models
timered
timeregulationknob
constant
strokespeedknob
on/offbutton