EasyManua.ls Logo

Emerson Daniel 3415

Emerson Daniel 3415
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configurations for open collector frequency outputs (continued)Table 3-1:
Cable
Cable re-
sistance Cable
Pull-up
resist-
ance Total
Maxi-
mum fre-
quency Sink
Cable
voltage
drop
0.5 16.8 10.00 500 516.8 5000 0.046 0.780
1 33.6 20.00 500 533.6 5000 0.045 1.511
1.7 57.12 34.00 500 557.12 5000 0.043 2.461
6.5 218.4 130.00 500 718.4 1000 0.033 7.296
The 22 AWG wire characteristics:
Capacitance = 20 pF/ft or 20 nF/1000 ft (between two wires)
Resistance = 0.0168 Ohms/ft or 16.8 Ohms/1000 ft
Pull-up voltage = 24 VDC
3.3 Grounding meter electronics housing
The meter electronics should be internally grounded for intrinsically safe operations.
Connect a wire to the chassis ground lug installed inside the Transmitter Electronics
Enclosure as the primary ground. A secondary ground is located outside of the Transmitter
Electronics Enclosure (see ).
NOTICE
The internal grounding terminal shall be used as the primary equipment ground. The external
terminal is only a supplemental bonding connection where local authorities permit or require
such a connection. DO NOT connect digital grounds to the ground lugs.
Electrical installation
46 Gas Ultrasonic Flow Meter

Table of Contents

Other manuals for Emerson Daniel 3415

Related product manuals