Pb3 and Pb4 configuration (Pb3 used for valve
1 and Pb4 used for valve 2)
0 = temperature (NTC probe)
1 = temperature (PTC probe)
2 = temperature (PT1000 probe)
3 = pressure (4÷20mA signal)
4 = pressure (0÷5V signal)
Relay 1 configuration (o1= active when the
contact is open; c1= when active the contact is
closed)
0= non used
1= active in case of circuit 1 probe error
2= active in case of MOP, LOP and circuit 1
probe error
3= active in case of high superheating, low
superheating, and circuit 1 probe error
4= active in case of MOP, LOP, high
superheating, low superheating and circuit 1
probe error
5= active in case of circuit 2 probe error
6= active in case of MOP, LOP and circuit 2
probe error
7= active in case of high superheating, low
superheating, and circuit 2 probe error
8= active in case of MOP, LOP, high
superheating, low superheating and circuit 2
probe error