1592026260 IEV22-24D GB r.1.0 21.02.2019 IEV 44/60
Ec 47
LAN address (used only if connected to the
IC200 EVO)
1
247
Ec 48
Map code (only reading)
0
9999
Ec 49
Firmware release (only reading)
Ec 50
Type of current valve 1: peak or RMS
0= peak
1= RMS
(this value is set automatically by the controller
if EC9> 0)
0
1
Ec 51
Type of signal valve 1: microstepping o normal
mode
0= microstepping
1= normal mode
(this value is set automatically by the controller
if EC9> 0)
0
1
Ec 52
Type of current valve 2: peak or RMS
0= peak
1= RMS
(this value is set automatically by the controller
if EC18> 0)
0
1
Ec 53
Type of signal valve 2: microstepping o normal
mode
0= microstepping
1= normal mode
(this value is set automatically by the controller
if EC18> 0)
0
1
Ec 54
Number of available gases selectable by Ec8
parameter.
This is an only reading parameter, used to
define the maximum value of Ec8 parameter.
1
247
Pr2
Password to enter in Pr2 level and password to
reset the alarm log
0
9999
Valve 1 configuration
Et 1
Number of steps the valve has to move before
compressor start-up.
0 = function is disabled
Ec14
Ec13
Full steps
Et 2
Sets valve manual operation mode
0= Automatic
1= Manual (valve is open to Et3 steps)
0
1
Et 3
Absolute number of steps the valve has to
move in manual mode
Ec14
Ec13
Full steps
Valve 2 configuration
Et 4
Number of steps the valve has to move before
compressor start-up.
0 = function is disabled
Ec23
Ec22
Full steps
Et 5
Sets valve manual operation mode
0= Automatic
1= Manual
0
1