3
August 2017
Installation and Maintenance Manual
E2K-402-0817 Rev. 2
Introduction
1.6 Short Term Storage
(Stored at Job Site less than one year from shipment)
1. Actuator should be stored with motor shaft in horizontal position and electrical
enclosure in either the horizontal or vertical position.
Figure 1
LSM
PWR
Cover
L
M
C
e
2. Actuator should be stored indoors free from job site dirt, mud, moisture and
temperature changes.
3. If indoor storage is not possible, the actuator must be stored off the ground above
possible water or snow level. Remove M2CP and store with other electrical and
electronic equipment in protected warehouse. If M2CP is not removed, Space
heater MUST be energized to protect electrical controls.
4. EIM supplies NPT plugs in each conduit entry. Do not remove until electrical hook-
up. The customer conduit should be routed to enter electrical enclosure at 1-1/2
(1.50) NPT located at lowest point, so condensation does not drain into enclosure
and damage parts.
5. Cover units loosely with a plastic sheet. This serves as partial protection from rain.
1.7 Long Term Storage
(Stored more than one year from shipment)
1. Store indoors or M2CP should be removed and stored in a protected area. Follow
procedures of short term storage.
WARNING:
Failure to store actuator properly ill void warranty of electical & electronic components.
Section 1: Introduction