Installation and Maintenance Manual
E2K-402-0817 Rev. 2
August 2017
M2CP Electrical Hook Up
Section 2: M2CP Electical Hook Up
Remove PWR and TBM covers to expose terminals for customer wiring. EIM Modular
Modular Control Package (M2CP) is available congured in many combinations of electrical
and electronic parts. Refer to WIRING DIAGRAM and EIM JOB SPEC SHEET for components
provided by EIM. Connect control wires to TBM and Power (motor) Voltage to PWR terminals.
If optional M2CP mounted circuit breaker was specied, connect power voltage leads to
circuit breaker. EIM terminal blocks are furnished with wire binding screw connectors with
rising captive plates, allowing eld connection by several methods: 1) strip and connect bare
wire, 2) strip and install wire ferrule, 3) strip and install crimp-on insulated or non-insulated
ring tongue or similar terminal. Circuit Breaker accepts 1) bare wire strip, or 2) wire ferrule.
Figure 2
bare wire strip
.400
.375
10 AWGmax
#8-32 (600V max)
bare wire strip
#6-32 (230Vmax
18-8 AWG (600V max)
.315
bare wire strip .450
7
60
Circuit
Breaker
PWR
Terminal s
TBM
Terminal s
Section 2: M2CP Electrical Hook Up