Installation, Operation and Maintenance Manual
VCIOM-15204-EN Rev. 1
May 2020
13
Section 12: Reverse Acting
(Counterclockwise to Close)
Standard factory actuators are normally set to clockwise rotation to close. However the
rotation can be reverse to counter-clockwise to close by simply reconguring the wiring
as follows:
Exchange 9 and 10 in main actuator terminal block
Exchange 11 and 12 in main actuator terminal block
If a PCU card is installed:
Exchange Potentiometer input wires P1(Orange wire) and P3 (Grey wire) on PCU
Change the direction of the indicator (HQ-200 and 300 only)
Recalibrate by using Auto Calibrate feature