FB1200 Flow Computer Quick Start Guide
D301786X012
November 2023
13
Grounding
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-
hazardous. Performing this operation in a hazardous area could result in an explosion.
The flow computer includes a ground lug on the terminal plate.
Once you have installed the unit, run a ground wire between the ground lug
and a known good earth ground. You route the ground wire through one of
the conduit fittings.
Use stranded copper wire to earth ground and keep the length as short as
possible.
Clamp or braze the ground wire to the ground bed conductor (typically a
stranded copper AWG 0000 cable installed vertically or horizontally).
Run the ground wire so that any routing bend in the cable has a minimum
radius of 30.48 cm (12 inches) below ground and 20.32 cm (8 inches) above
ground.
For more information on grounding or if your installation uses cathodic
protection, refer to Site Considerations for Equipment Installation, Grounding,
and Wiring (D301452X012).