Introduction and Specifications
December 2009
1-5
Table 1-1. Specifications
Available Configurations
DVC6010f: Sliding-stem applications
DVC6020f: Rotary and long-stroke sliding-stem
applications [over 102 mm (4 inch) travel]
DVC6030f: Quarter-turn rotary applications
Remote-Mounted Instrument
(1)
DVC6005f: Base unit for 2 inch pipestand or wall
mounting
DVC6015: Feedback unit for sliding-stem
applications
DVC6025: Feedback unit for rotary or long-stroke
sliding-stem applications
DVC6035: Feedback unit for quarter-turn rotary
applications
DVC6000f digital valve controllers can be mounted
on Fisher and other manufacturers rotary and
sliding-stem actuators.
Function Block Suites
Standard Control (throttling control)
Includes AO, PID, ISEL, OS, AI, MAI, DO, and four
DI function blocks
Fieldbus Control (throttling control)
Contains the AO function block
Fieldbus Logic [discrete on/off]
Includes DO, and four DI function blocks
Block Execution Times
AO Block: 15 ms AI Block: 15 ms
PID Block: 20 ms MAI BLock: 35 ms
ISEL Block: 20 ms DO Block: 15 ms
OS Block: 20 ms DI Block: 15 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
FOUNDATION fieldbus registered device
Physical Layer Type(s):
121—Low−power signaling, bus−powered, Entity
Model I.S.
511—Low−power signaling, bus−powered, FISCO
I.S.
Fieldbus Device Capabilities
Backup Link Master capable
Device Description Compatibility
Firmware Revision DD Compatibility
2.0 2 and 3
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure.
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single direct, and Single reverse
Supply Pressure
(2)
Recommended: 0.3 bar (5 psi) higher than
maximum actuator requirements, up to maximum
supply pressure
Maximum: 10 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Medium: Air or Natural Gas
(3)
Air Quality: Supply pressure must be clean, dry air
that meets the requirements of ISA Standard
7.0.01. A maximum 40 micrometer particle size in
the air system is acceptable. Further filtration down
to 5 micrometer particle size is recommended.
Lubricant content is not to exceed 1 ppm weight
(w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized
Natural Gas: Natural gas must be clean, dry,
oil-free, and noncorrosive. H
2
S content should not
exceed 20 ppm.
Steady-State Air Consumption
(4,5)
Standard Relay: At 1.4 bar (20 psig) supply
pressure: Less than 0.38 normal m
3
/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
normal m
3
/hr (49 scfh)
Low Bleed Relay: At 1.4 bar (20 psig) supply
pressure: Average value 0.056 normal m
3
/hr
(2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
0.184 normal m
3
/hr (6.9 scfh)
Maximum Output Capacity
(4,5)
At 1.4 bar (20 psig) supply pressure:
10.0 normal m
3
/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure:
29.5 normal m
3
/hr (1100 scfh)
−continued−