DVC6000f Series
March 2006
5-54
Table 5-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
INST_ALERTS_ENABLE
75
Elect Enable
ELECT_ENABLE
75.1 RW ALL
0: Drive Current
1: Drive Signal
2: Program Memory
3: Static Memory
4: Processor
5: I/O Processor
6: Output Block Timeout
7: Blocks Set to Defaults
Enabled Bits:
0: Drive Current
1: Drive Signal
2: Program
Memory
3: Static Memory
4: Processor
5: I/O Processor
7: Block Set to
Default
SETUP
Data Type: Bit String
0=disable
1=enable
Electronic Alerts Enable
Sensor Enable
SENSOR_ENABLE
75.2 RW ALL
0: Travel Sensor
1: Port A Pressure
Sensor
2: Port B Pressure
Sensor
3: Supply Pressure
Sensor
4: Temperature Sensor
Enabled Bits:
0: Travel Sensor
1: Port A
Pressure Sensor
2: Port B
Pressure Sensor
3: Supply
Pressure Sensor
4: Temperature
Sensor
SETUP
Data Type: Bit String
0=disable
1=enable
Sensor Alerts Enable
Enviro Enable
ENVIRO_ENABLE
75.3 RW ALL
0: Supply Pressure High
1: Supply Pressure Low
2: Temperature High
3: Temperature Low
Enabled Bits:
0: Supply
Pressure High
2: Temperature
High
3: Temperature
Low
SETUP
Data Type: Bit String
0=disable
1=enable
Enviro Alerts Enable
Travel Enable
TRAVEL_ENABLE
75.4 RW ALL
0: Travel Deviation
1: Travel Limit High High
2: Travel Limit Low Low
3: Travel Limit High
4: Travel Limit Low
Enabled Bits:
0: Travel
Deviation
SETUP
Data Type: Bit String
0=disable
1=enable
Travel Alerts Enable
Prox Enable
PROX_ENABLE
75.5 RW ALL
0: Travel Open
1: Travel Closed
2: Proximity High High
3: Proximity High
4: Proximity Low
5: Proximity Low Low
All bits: 0 SETUP
Data Type: Bit String
0=disable
1=enable
Proximity Alerts Enable
Tvl History Enable
TVL_HISTORY_ENABLE
75.6 RW ALL
0: Cycle Counter
1: Travel Accumulator
All bits: 0 SETUP
Data Type: Bit String
0=disable
1=enable
Travel History Alerts Enable
Performance Enable
PERF_ENABLE
75.7 RW ALL
0: Performance Critical
1: Performance
Reduced
2: Performance
Information
Enabled Bits:
0: Performance
Critical
1: Performance
Reduced
SETUP
Data Type: Bit String
0=disable
1=enable
Performance Alerts Enable
Continued
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals