Viewing Device Information
March 2006
7-7
Device Record
(TB > Display > Device Record )
The following parameters are contained in the Device
Record menu of the transducer block.
Temp Max
Temperature Maximum (TEMP_MAX [86.1]) shows
the maximum temperature the instrument has
experienced since installation.
Temp Max Time
Temperature Maximum Time (TEMP_MAX_TIME
[86.2]) shows the date and time when the Temp Max
occurred.
Temp Min
Temperature Minimum (TEMP_MIN [86.3]) shows the
minimum temperature the instrument has experienced
since installation.
Temp Min Time
Temperature Minimum Time (TEMP_MIN_TIME
[86.4]) shows the date and time when the Temp Min
occurred.
Supp Press Max
Supply Pressure Maximum (SUPPLY_PRESS_MAX
[86.5]) shows the maximum supply pressure the
instrument has experienced since installation.
Supp Press Max Time
Supply Pressure Maximum Time
(SUPP_PRESS_MAX_TIME [86.6]) shows the date
and time when the Supp Press Max occurred.
Supp Press Min
Supply Pressure Minimum (SUPP_PRESS_MIN
[86.7]) shows the minimum supply pressure the
instrument has experienced since installation.
Supp Press Min Time
Supply Pressure Minimum Time
(SUPP_PRESS_MIN_TIME [86.8]) shows the date
and time when the Supp Press Min occurred.
Block Errors
Table 7-2 lists conditions reported in the BLOCK_ERR
[6] and XD_ERROR [11] parameters. Conditions in
italics are not applicable for the transducer block and
are provided only for your reference.
Table 7-2. Transducer Block BLOCK_ERR and
XD_ERROR Conditions
Condition
Number
Condition Name and Description
0 Other - (N/A)
1
Block Configuration Error - Indicates that one of the
following parameters have been configured out of the
proper range: 15, 16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2 Link Configuration Error - (N/A)
3
Simulate Active - Indicates that the simulation jumper is
in place on the aux terminals. This is not an indication
that the I/O blocks are using simulation data. See AO
block paramter SIMULATE [10] and DO block parameter
SIMULATE_D [10].
4 Local Override - (N/A)
5 Device Fault State − (NA)
6 Maintenance Needed Soon - (N/A)
7 Input failure/process variable has Bad status - (N/A)
8 Output failure - (N/A)
9 Memory failure - (N/A)
10
Lost Static Data - Indicates that manufacturing functional
or thermal tests were incomplete
11 Lost NV Data - (N/A)
12 Readback Check Failed - (N/A)
13
Device Needs Maintenance Now - Indicates that
manufacturing functional or thermal tests were incomplete
14 Power Up - (N/A)
15 Out of Service - Indicates Out of Service Mode.
7