Viewing Device Information
March 2006
7-7
Device Record
(TB > Display > Device Record )
The following parameters are contained in the Device
Record menu of the transducer block.
Temp Max
Temperature Maximum (TEMP_MAX [86.1]) shows
the maximum temperature the instrument has
experienced since installation.
Temp Max Time
Temperature Maximum Time (TEMP_MAX_TIME
[86.2]) shows the date and time when the Temp Max
occurred.
Temp Min
Temperature Minimum (TEMP_MIN [86.3]) shows the
minimum temperature the instrument has experienced
since installation.
Temp Min Time
Temperature Minimum Time (TEMP_MIN_TIME
[86.4]) shows the date and time when the Temp Min
occurred.
Supp Press Max
Supply Pressure Maximum (SUPPLY_PRESS_MAX
[86.5]) shows the maximum supply pressure the
instrument has experienced since installation.
Supp Press Max Time
Supply Pressure Maximum Time
(SUPP_PRESS_MAX_TIME [86.6]) shows the date
and time when the Supp Press Max occurred.
Supp Press Min
Supply Pressure Minimum (SUPP_PRESS_MIN
[86.7]) shows the minimum supply pressure the
instrument has experienced since installation.
Supp Press Min Time
Supply Pressure Minimum Time
(SUPP_PRESS_MIN_TIME [86.8]) shows the date
and time when the Supp Press Min occurred.
Block Errors
Table 7-2 lists conditions reported in the BLOCK_ERR
[6] and XD_ERROR [11] parameters. Conditions in
italics are not applicable for the transducer block and
are provided only for your reference.
Table 7-2. Transducer Block BLOCK_ERR and
XD_ERROR Conditions
Condition
Number
Condition Name and Description
0 Other - (N/A)
1
Block Configuration Error - Indicates that one of the
following parameters have been configured out of the
proper range: 15, 16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2 Link Configuration Error - (N/A)
3
Simulate Active - Indicates that the simulation jumper is
in place on the aux terminals. This is not an indication
that the I/O blocks are using simulation data. See AO
block paramter SIMULATE [10] and DO block parameter
SIMULATE_D [10].
4 Local Override - (N/A)
5 Device Fault State (NA)
6 Maintenance Needed Soon - (N/A)
7 Input failure/process variable has Bad status - (N/A)
8 Output failure - (N/A)
9 Memory failure - (N/A)
10
Lost Static Data - Indicates that manufacturing functional
or thermal tests were incomplete
11 Lost NV Data - (N/A)
12 Readback Check Failed - (N/A)
13
Device Needs Maintenance Now - Indicates that
manufacturing functional or thermal tests were incomplete
14 Power Up - (N/A)
15 Out of Service - Indicates Out of Service Mode.
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals