Installation
March 2006
2-3
Installation
WARNING
Avoid personal injury or property
damage from sudden release of
process pressure or bursting of parts.
Before mounting the DVC6000f Series
digital valve controller:
Always wear protective clothing
and eyewear when performing any
installation procedures.
Disconnect any operating lines
providing air pressure, electric power,
or a control signal to the actuator. Be
sure the actuator cannot suddenly
open or close the valve.
Use bypass valves or completely
shut off the process to isolate the
valve from process pressure. Relieve
process pressure from both sides of
the valve.
Vent the pneumatic actuator
loading pressure and relieve any
actuator spring precompression.
Use lock-out procedures to be
sure that the above measures stay in
effect while you work on the
equipment.
Check with your process or
safety engineer for any additional
measures that must be taken to
protect against process media.
Special Instructions for Safe Use and
Installation in Hazardous Locations
Certain nameplates may carry more than one
approval, and each approval may have unique
installation requirements and/or conditions of safe-use.
Special instructions are listed by agency/approval
below.
After reading and understanding these special
conditions of use, proceed with standard installation
procedures.
WARNING
Failure to follow these conditions of
safe-use could result in personal injury
or property damage from fire or
explosion, and area re-classification.
CSA
Special Conditions of Safe Use
No special conditions for safe use.
Refer to table 1-3 for approval information, figures D-1
and D-2 for CSA loop schematics, and figure D-3 for
the CSA nameplates.
FM
Special Conditions of Safe Use
No special conditions for safe use.
Refer to table 1-4 for approval information, figures D-4
and D-5 for FM loop schematics, and figure D-6 for the
FM nameplates.
ATEX Intrinsic Safety, Dust
Special Conditions for Safe Use
Type DVC6000f Series, and Type DVC6005f
1. This apparatus can only be connected to an
intrinsically safe certified equipment and this
combination must be compatible as regards the
intrinsically safe rules.
2. The electrical parameters of this equipment must
not exceed any following values:
U
O
v 17.5 V; I
O
v380 mA; P
O
v 5.32 W
3. Operating ambient temperature: −52C or −40C
to + 85C
Type DVC6015, DVC6025, and DVC6035
1. This apparatus can only be connected to an
instrinsically safe certified equipment and this
combination must be compatible as regards the
intrinsically safe rules.
Refer to table 1-5 for additional approval information,
and figure D-7 for the the ATEX Intrinsic Safety, Dust
nameplates.