EasyManuals Logo

Emerson Fisher Fieldvue DVC6020f User Manual

Emerson Fisher Fieldvue DVC6020f
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #270 background imageLoading...
Page #270 background image
DVC6000f Series
March 2006
8-2
Figure 8-1. DVC6000f Series Digital Valve Controller Block Diagram
E0408-1 / IL
DIGITAL
SETPOINT
9–32 VOLT
FIELDBUS
SUPPLY
PRESSURE
PRINTED
WIRING BOARD
PNEUMATIC
RELAY
I/P
CONVERTER
OUTPUT A
OUTPUT B
VALVE TRAVEL
FEEDBACK
AUXILIARY
TERMINALS
TERMINAL BOX
DRIVE
SIGNAL
VALVE AND ACTUATOR
DIRECT ACTING RELAY TYPE A
ZERO POWER CONDITION = VALVE CLOSED
Digital Valve Controller Operation
DVC6000f Series digital valve controllers have a single
module base that may be easily replaced in the field
without disconnecting field wiring or tubing. The
master module contains the following submodules:
current-to-pneumatic (I/P) converter, printed wiring
board assembly, and pneumatic relay. The master
module can be rebuilt by replacing the submodules.
See figures 8-1 and 8-2.
DVC6000f Series digital valve controllers are
bus-powered instruments that provide a control valve
position in response to a digital setpoint from the
control room. The following describes a direct acting
Type DVC6010f digital valve controller mounted on a
sliding stem piston actuator, where the valve is closed
with zero power to the instrument.
The setpoint is routed into the terminal box through a
single pair of wires and then to the printed wiring
board assembly submodule where it is read by the
microprocessor, processed by a digital algorithm, and
converted into an analog I/P drive signal.
As the setpoint increases, the drive signal to the I/P
converter increases, increasing the I/P output
pressure. The I/P output pressure is routed to the
pneumatic relay submodule. The relay is also
connected to supply pressure and amplifies the small
pneumatic signal from the I/P converter. The relay
accepts the amplified pneumatic signal and provides
two output pressures. With Relay Type A, an
increasing setpoint will produce increasing pressure at
output A and decreasing pressure at output B (with
Relay Type B only output A is available and is
reversed). The output A pressure is used for
double-acting and single-acting direct applications.
The output B pressure is used for double-acting and
single-acting reverse applications.
8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals