DVC6000f Series
March 2006
4-4
Table 4-2. Actuator Information for Basic Setup
Actuator
Manufacturer
Actuator
Model
Actuator Size Actuator Style
Starting
Tuning
Set
Feedback
Connection
Travel Sensor Motion
(Relay A)
(1)
Fisher
585C & 585CR
25
50, 60
60, 80
100, 130
Piston Dbl w/ or w/o
Spring. See actuator
instruction manual and
nameplate.
F
J
L
M
SStem-Standard
for travels up to
4 inches. SStem-
Roller for longer
travels
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
657
30
34, 40
45, 50
46, 60, 70, 76,
& 80-100
Spring & Diaphragm
H
K
L
M
SStem-Standard Clockwise
667
30
34, 40
45, 50
46, 60, 70, 76,
& 80-100
Spring & Diaphragm
H
K
L
M
SStem-Standard Counterclockwise
1051 & 1052
20, 30
33
40
60, 70
Spring & Diaphragm
H
I
K
M
Rotary Clockwise
1061
30
40
60
68, 80, 100 &
130
Piston Dbl w/o Spring
J
K
L
M
Rotary
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
1066 20, 27, 75 Piston Dbl w/o Spring Specify Rotary
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
1066SR
20
27, 75
Piston Sgl w/Spring
G
L
Rotary
Mounting Style
Travel Sensor
Motion
A Clockwise
B Counterclockwise
C Counterclockwise
D Clockwise
GX
225
Spring & Diaphragm
X
(2)
SStem-Standard
Air to
750 K Open Close
1200 M Counterclockwise Clockwise
Baumann
Air to Extend
16
32
570
Spring & Diaphragm
C
E
K
SStem-Standard Clockwise
Air to Retract
16
32
570
Spring & Diaphragm
C
E
K
SStem-Standard Counterclockwise
Rotary
10
25
54
E
H
J
Rotary Specify
Gulde
3024
GA 1.21
GA 1.31
GA 1.41
Spring & Diaphragm
E
H
K
SStem-Standard
For P
o
operating mode (air opens),
Counterclockwise
For P
s
operating mode (air closes),
Clockwise
3025
P460, P462,
P900
M Rotary Specify
1. Values shown are for Relay Type A. Reverse for Relay Type B.
2. X = Expert tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
4

Table of Contents