GFK-2738AE Jan 2024
7
Problems Resolved by this Revision
IC695PNSx01
Overtemperature resets
The IC695PNS001-Bxxx or IC695PNS101 could incorrectly indicate an
overtemperature condition and reset even when the operating
temperature is within normal ranges.
Functional Compatibility
The following CPU firmware, programming software, and backplane hardware versions are required to use the
features introduced in the most recent PNS release:
Minimum PNS
Version Required
Single fiber break
detection
PNS001-Bxxx/PNS101
Release 3.40
CPE330 Release 10.30
CPE400/CPL410 Release 10.30
CPE302/305/310 Release 10.30
IC695CMM002/004,
IC695PSD180 support
PNSx01-Bxxx/PNS101
Release 3.35
CPE330 Release 10.30
CPE400/CPL410 Release 10.30
CPE302/305/310 Release 10.30
Sequence of Events
with Five PNS101s
CPE330 Release 10.15
CPE400/CPL410 Release 10.15
PNS101 &
CPE400/CPL410
Sequence of Events
with MDL655/MDL660
CPE400/CPL410 Release 10.10
PNS101 & CPE330
Sequence of Events
with MDL655
PNS101 & CPE330
Sequence of Events
with MDL660
CPU320/CPU315 Release 8.95
CPE310/CPE305 Release 8.95
CRU320 Release 8.95
CPE330 Release 8.95
CPE400 Release 9.00
CPL410 Release 9.55
CPE100 Release 9.15
CPE115 Release 9.45
RXi Controller Release 7.80
9
PNS001-Axxx
(Most Recent Release)
CPU320/CPU315 Release 8.95
CPE310/CPE305 Release 8.95
HART Pass Through COMMREQ feature not supported on RXi Controller. Refer to future RXi Controller IPI for updates.