EasyManua.ls Logo

Emerson iPro.Genius - Relay Output Overrides with Visograph

Emerson iPro.Genius
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Discharge Air Controller (DAC) Manual Connections • 33
9.2. Terminal Number Descriptions
Terminal
No.
Type of Input Description
1 Supply Power 24VAC or 24VDC(-)
2 Pb1 Analog Input 1 (Temperature, 0-10V, 0-1V, 0-5V)
3 Pb2 Analog Input 2 (Temperature, 0-10V, 0-1V, 0-5V)
4 Pb3 Analog Input 3 (Temperature, 0-10V, 0-1V, 0-5V)
5 Pb4 Analog Input 4 (Temperature, 0-10V, 0-1V, 0-5V)
6 Pb5 Analog Input 5 (Temperature, 0-10V, 0-1V, 0-5V)
7 PbC Common for temperature inputs (DO NOT TIE TO GROUND
)
8 GND(-) Additional power reference 5VDC and 12VDC and analog inputs (0 -10V,
0 -1V, 0 -5V)
9 Supply Power 24VAC or 24VDC(+)
10 Pb6 Analog Input 6 (Temperature, 0-10V, 0-1V, 0-5V)
11 Pb7 Analog Input 7 (Temperature, 0-10V, 0-1V, 0-5V)
12 Pb8 Analog Input 8 (Temperature, 0-10V, 0-1V, 0-5V)
13 Pb9 Analog Input 9 (Temperature, 0-10V, 0-1V, 0-5V)
14 Pb10 Analog Input 10 (Temperature, 0-10V, 0-1V, 0-5V)
15 +5V Additional power +5VDC
16 +12V Additional power +12VDC
21 Out1 Opto-insulated analog output 1, 0-10V
22 Out2 Opto-insulated analog output 2, 0-10V
23 Out3 Opto-insulated analog output 3, 0-10V
24 Out4 Opto-insulated analog output 4, 0-10V
25 GND(-) Common opto-insulated analog output
26 Out5 analog output 5, 0-10V
27 Out6 analog output 6, 0-10V
28 Supply Power for opto-insulated analog outputs at 24VAC or 24VDC(-)
29 Supply Power for opto-insulated analog outputs at 24VAC or 24VDC(+)
30 GND(-) Common opto-insulated analog output
40 DI1 Opto-insulated digital input 1
41 DI2 Opto-insulated digital input 2
42 DI3 Opto-insulated digital input 3
43 DI4 Opto-insulated digital input 4
44 DI5 Opto-insulated digital input 5
45 DI6 Opto-insulated digital input 6
46 DI7 Opto-insulated digital input 7
Table 9-2 - Terminal Number Descriptions

Table of Contents

Related product manuals