Installation (Applicable to all Models)
16
Figure 10 Piping connections for chilled water self-contained units - Downflow models
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Condensate Drain
3/4" FPT
Field pitch a minimum
of 1/8" (3.2mm) per ft. (305mm).
The drain line must comply
with all applicable codes.
Humidifier Water Supply Line
1/4" OD CU
Chilled Water Return Line
1-1/8" OD CU
Hot Water Return
5/8" OD CU (optional)
Chilled Water Supply Line
1-1/8" OD CU
Hot Water Supply
5/8" OD CU (optional)
DPN000371
Rev. 01
Liebert iCOM
Control