EasyManua.ls Logo

Emerson Liebert Challenger 3000 - Control Types; Temperature and Humidity Control Types

Emerson Liebert Challenger 3000
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Air-Cooled Models—Self-Contained Compressor
24
Figure 14 Air-cooled condensers
Table 4 Air-cooled condenser statistics
Model
Number
of Fans
Connection Sizes
(OD Copper)
Net Weight
lb (kg)
“A” Dimension
in (mm)Hot Gas (in.) Liquid (in.)
083 1 7/8 5/8 295 (133.8) 42 (1067)
104 1 1-1/8 5/8 315 (142.8) 42 (1067)
165 2 1-1/8 7/8 425 (193) 82 (2083)
Secure each leg to condenser frame at all
points shown using hardware provided.
Liquid line
* B
TYPICAL FOOTPRINT
Liebert Lee-Temp heater
pad connection box
*B - Inverted traps are to be field-supplied and installed
(typ). When installing traps, provide clearance for swing
end of access door. Traps are to extend above base of
coil by a minimum of 7-1/2" (190 mm)
Liquid line
Hot gas line
Electric service
supplied by
others
Electric
service
supplied by
others
Hot gas
line
* B
LIEBERT LEE-TEMP CONDENSER
FAN SPEED AND VFD CONDENSER
44"
(1118mm)
18" (457.2mm)
43-9/16"
(1106mm)
51-7/16"
(1306.5mm)
37-7/8"
(962mm)
Common to all models. See Table 4
below for key to “A” dimension.
CONDENSER MOUNTING
1"
(25.4mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1"
(25.4mm)
1-3/4"
(44.5mm)
1" typ.
(25.4mm)
1-3/4"
(44.5mm)
37-11/16"
(957.3mm)
1-3/4"
(44.5mm)
A
9/16" (14.3mm)
diameter holes
8 places for
1/2" (12.7mm)
diameter bolts
43-3/16"
(1097mm)
SINGLE FAN AIR-COOLED CONDENSERS
1" typ.
(25.4mm)

Table of Contents