Emerson Liebert Challenger 3000 - Figure 42 3-Ton Water;Glycol-Cooled Condensing Unit (Cont.)

Emerson Liebert Challenger 3000
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Split System Models
74
Figure 42 3-ton water/glycol-cooled condensing unit (con't.)
DPN000209_Rev0
Single- or
three-phase
electric service
not by Liebert
Field-supplied unit disconnect
switch when optional disconnect
is not provided in unit
Field-supplied 24V NEC Class 1
wiring to fan/coil unit
Field-supplied 24V NEC Class 1
wiring to drycooler
(glycol-cooled units only)
Earth/ground connection
Connection terminal for field-supplied
earth-grounding wire
Line-voltage electric
power supply entrance
Factory-wired components
on electric panel
Optional factory-installed
disconnect switch
Low-voltage electric
power supply entrance
Remote drycooler connection
Terminals 70 & 71 supplied
for connection to remote drycooler
Use field-supplied 24V NEC Class 1
wiring (glycol-cooled units only)
Heat rejection connection.
Field-supplied 24V NEC Class 2 wiring.
Wire connections from evaporator mod:
1. 24V GND
2. 24V supply
3. High-pressure alarm (optional)
4. Hot gas bypass connection
(only on units with hot-gas bypass)
NOTES
1. Refer to specification sheet for full load amp
and wire size amp ratings.
2. Control voltage wiring must be a minimum
of 16 GA (1.6mm) for up to 75' (23m) or
not to exceed 1 volt drop in control line.