What to do if Emerson Liebert GXT MT+LB 10KL UPS is overloaded?
- AAnthony AdamsAug 22, 2025
If your Emerson UPS is overloaded, remove some of the loads from the UPS output.

What to do if Emerson Liebert GXT MT+LB 10KL UPS is overloaded?
If your Emerson UPS is overloaded, remove some of the loads from the UPS output.
What to do if my Emerson Liebert GXT MT+LB 10KL UPS displays Warning 10?
If your Emerson UPS displays Warning 10, it means the input fuse on the power stage board is blown. Check and replace the input fuse.
What to do if my Emerson Liebert GXT MT+LB 10KL shows Warning 0B?
If your Emerson UPS displays Warning 0B, it means that the EPO plug (jumper) is removed or the external EPO switch is off. Connect the EPO plug (jumper) well or switch on the external EPO switch.
What to do if my Emerson Liebert GXT MT+LB 10KL fan is blocked (Warning 0A)?
If the fan in your Emerson UPS is blocked, clean it to ensure it is not obstructed. If the fan is at the end of its life or the fan circuit has failed, contact the dealer for repair.
What to do if my Emerson Liebert GXT MT+LB 10KL displays Warning 07?
If your Emerson UPS displays Warning 07, it means that the battery number and its setting is not matching or the charger voltage is too high. To solve the problem: 1. Correct the battery number or its setting. 2. Disconnect the battery and check the charger output voltage. Then, contact the dealer for repair.
What to do if my Emerson Liebert GXT MT+LB 10KL displays Warning 01?
If your Emerson UPS shows Warning 01, it indicates a battery issue. This could be due to the battery not being connected properly or the battery protection device being open. To resolve this: 1. Ensure the battery is well connected. 2. Replace or restore the protection device.
What to do if Emerson UPS output has a short circuit (Fault 14)?
If a short circuit occurs on the Emerson UPS output, remove the short-circuited component or correct the situation that caused it. If the problem persists, contact the dealer for repair.
What to do if my Emerson Liebert GXT MT+LB 10KL shows Warning 08?
If your Emerson UPS displays Warning 08, it could be due to several reasons: the battery is deeply discharged, the battery number is incorrect, or the battery is at the end of its life. Try these steps: 1. Recharge the battery. 2. Correct the battery number. 3. Replace the battery.
What to do if my Emerson Liebert GXT MT+LB 10KL UPS is locked in bypass after overload (Warning 33)?
If your Emerson UPS is locked in bypass after an overload, remove excess loads from the UPS output. Then, shut down the UPS and restart it.
What to do if my Emerson Liebert GXT MT+LB 10KL UPS has high internal temperature (Warning 0D)?
If the internal temperature of your Emerson UPS is too high, ensure the ambient temperature is not over 40°C, the fan is working correctly, and ventilation is unobstructed. If possible, remove some loads.
Key operational safety guidelines, including earth conductor, live parts, and foreign objects.
Crucial safety instructions and requirements for installing the UPS system correctly.
Step-by-step guide for installing a single UPS unit, including wiring and safety precautions.
Details on the function of each button on the UPS control panel.
Describes the different audible alarms, their causes, and buzzer status.
Step-by-step guide for operating a single UPS unit with utility power and connecting devices.
Describes warning indicators, fault codes, and how to interpret them.
Explanation of the UPS's LED indicators and the LCD panel layout.
Explains fault indications, causes, and immediate actions for critical errors.
Details common UPS warnings, their codes, possible causes, and recommended remedies.
Details common UPS faults, their codes, possible causes, and recommended remedies.
Important safety precautions and general guidelines for UPS maintenance by qualified personnel.