Installation
11
2.0 INSTALLATION
2.1 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and
your local dealer or your Emerson representative immediately.
Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Emerson representative immediately.
2.2 What’s Included
With GXT3 UPS
Compact Disk with:
Liebert MultiLink
Configuration Program
User Manual
USB Cable: one, 6-1/2 ft. (2m) long
Mounting hardware, including screws and handles
Plastic tower stand sets: 2 (four pieces)
Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
2.3 Preparation for Installation
2.3.1 Installation Environment
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.
The installation environment should meet the specifications listed in 9.0 - Specifications).
Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids,
gases, corrosives, and conductive contaminants. Avoid direct sunlight.
Installation Clearances
Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not
obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
2.4 Mechanical Installation
The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use consider-
ations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery cabinets.
NOTE
The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
spacers for tower configuration and one DC power cable.
NOTE
Operating the Liebert GXT3 in temperatures above 77°F (25°C) reduces battery life.
NOTE
When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Liebert GXT3 Series and is the answer not in the manual?

Emerson Liebert GXT3 Series Specifications

General IconGeneral
ModelLiebert GXT3 Series
Frequency50/60 Hz
TypeOnline Double Conversion
Power Capacity1kVA to 10kVA
Input Voltage120V, 208V, 230V (depending on the specific model)
Output Voltage120V, 208V, 230V (depending on the specific model)
Backup TimeVaries by model and load
Form FactorTower/Rackmount
Operating Temperature0 to 40°C (32 to 104°F)
Humidity0% to 95% (non-condensing)
DimensionsVaries depending on the specific model
WeightVaries by model
Battery TypeValve-regulated lead acid (VRLA)

Related product manuals