EasyManuals Logo

Emerson Liebert GXT3 Series User Manual

Emerson Liebert GXT3 Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
Specifications
38
Table 14 Battery run times
Number of
Batteries
Model
VA
1
Run Time, Minutes, for Load, W
200 400 600 800 1000 1200 1400 1600 1800 2000 2500
100% Load
Min. W
Internal
Battery
500VA3012——————— 8450
700VA26146——————— 6630
1000VA281595——————— 4900
1500VA2616108 5 ————— 41350
2000VA 20 11 10 8 6 5 4 4 1800
3000VA 25201410985442700
Internal
Battery
+ 1External
Battery
Cabinet
500VA13080———————66450
700VA1267854———————50630
1000VA128745241———————27900
1500VA11072483628—————241350
2000VA 54 34 34 26 22 17 15 15 1800
3000VA 102 80 56 50 44 38 26 22 18 2700
Internal
Battery
+ 2External
Battery
Cabinets
500VA220130———————116450
700VA26412288———————82630
1000VA2521268460———————58900
1500VA208132947454—————481350
2000VA120826052443629291800
3000VA 124 114 106 92 74 66 62 46 44 2700
Internal
Battery
+ 3 External
Battery
Cabinets
500VA336150———————128450
700VA280140120———————116630
1000VA32014811880———————78900
1500VA31020413810290—————821350
2000VA 180 126 92 72 62 52 45 45 1800
3000VA 174 150 122 110 105 104 76 62 62 2700
Internal
Battery
+ 4 External
Battery
Cabinets
500VA630210———————174450
700VA560300146———————140630
1000VA600250138116———————109900
1500VA400256180144110—————1001350
2000VA 240 166 130 108 94 84 64 64 1800
3000VA 184 172 150 128 120 119 105 92 84 2700
1. Run times are valid for all models rated with the listed VA.
2. Approximate discharge times are in minutes and at 77°F (25°C) with a resistive load.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Liebert GXT3 Series and is the answer not in the manual?

Emerson Liebert GXT3 Series Specifications

General IconGeneral
ModelLiebert GXT3 Series
Frequency50/60 Hz
TypeOnline Double Conversion
Power Capacity1kVA to 10kVA
Input Voltage120V, 208V, 230V (depending on the specific model)
Output Voltage120V, 208V, 230V (depending on the specific model)
Backup TimeVaries by model and load
Form FactorTower/Rackmount
Operating Temperature0 to 40°C (32 to 104°F)
Humidity0% to 95% (non-condensing)
DimensionsVaries depending on the specific model
WeightVaries by model
Battery TypeValve-regulated lead acid (VRLA)

Related product manuals