EasyManua.ls Logo

Emerson Micro Motion 4700 - Communicating with the Transmitter

Emerson Micro Motion 4700
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7  Communicating with the transmitter
Use either the HART terminals connected to ProLink III or Trex unit to download or upload
data from/to the transmitter, because the service port is for factory use only.
Procedure
1. To connect to the transmitter terminals or to the HART connection posts:
a)
Remove the transmitter end-cap.
b) Attach the leads from the Field Communicator to terminals 1 and 2 on the
transmitter, or to the HART connection posts, and add resistance as required.
The Field Communicator must be connected across a resistance of 250–600 Ω.
Tip
HART connections are not polarity-sensitive. It does not matter which lead
you attach to which terminal.
Figure 7-1: Field Communicator connection to transmitter terminals
A. Field Communicator
B. 250–600 Ω resistance
C. External power supply, if required
D. Transmitter with end-cap removed
2. Turn on the Field Communicator and wait until the main menu is displayed.
Installation Manual Communicating with the transmitter
00825-0100-5710 October2023
Installation Manual 43

Related product manuals