56 Powerdrive F300 Getting Started Guide
Issue Number: 5
00.049 User Security Status {11.044}
Menu 0 (0), All Menus (1),
Read-only Menu 0 (2),
Read-only (3), Status Only (4),
No Access (5)
Menu 0 (0) RW Txt ND PT
00.050 Software Version {11.029} 0 to 99999999
RO Num ND NC PT
00.051
Action On Trip
Detection
{10.037} 00000 to 11111 00000 RW Bin US
00.052
Reset Serial
Communications
{11.020} Off (0) or On (1) Off (0) RW Bit ND NC
00.053
Motor Thermal
Time Constant 1
{04.015} 1.0 to 3000.0 s 89.0 s RW Num US
00.054
RFC Low
Speed Mode
{05.064}
Injection (
0), Non-
salient
(1)
Non-
salient
(1)
RW Txt US
00.055
Low Speed
Sensorless
Mode Current
{05.071}
0.0 to
1000.0 %
20.0 % RW Num RA US
00.056 No-load Lq {05.072}
0.000 to
500.000
mH
0.000
mH
RW Num RA US
00.057
Iq Test Current
or Inductance
Measurement
{05.075}
0to
200 %
100 % RW Num US
00.058
Phase Offset At
Iq Test Current
{05.077}
±90.0 ° 0.0 ° RW Num RA US
00.059
Lq At The
Defined Iq
Test Current
{05.078}
0.000 to
500.000
mH
0.000
mH
RW Num RA US
00.060
Id Test
Current for
Inductance
Measurement
{05.082}
-100 to
0 %
-50 % RW Num US
00.061
Lq At The
Defined Id Test
Current
{05.084}
0.000 to
500.000
mH
0.000
mH
RW Num RA US
RW
Read /
Write
RO
Read
only
Num
Number
parameter
Bit
Bit
parameter
Txt
Text
string
Bin
Binary
parameter
FI Filtered
ND
No
default
value
NC
Not
copied
PT
Protected
parameter
RA
Rating
dependent
US
User
save
PS
Power-down
save
DE Destination
Parameter
Range Default
Type
OL RFC-A RFC-S OL RFC-A RFC-S