Powerdrive F300 Getting Started Guide 73
Issue Number: 5
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Basic parameters
(Menu 0)
Running the
motor
Optimization
NV Media Card
Operation
Further
information
UL listing
information
Check
Saliency
In sensorless mode, when the motor speed is below Pr
00.045
/ 10, a
special low speed algorithm must be used to control the motor. There are
two modes available, with the mode chosen based on the saliency of the
motor. The Dyneo LSRPM motors have little or no saliency so require the
non-salient low speed mode to be used. Set Pr
00.054
to: Non-salient (1).
Non-salient mode requires the ramp rate to be no slower than 5 s / 1000
rpm when operating in the region below Rated Speed Pr
00.045
/ 10. The
drive contains a feature to ensure that the ramp rate during the low speed
region is at least 4 s / 1000 rpm. This feature is enabled automatically
after a successful set-up of the Dyneo LSRPM motor.
Save
parameters
Select 'Save Parameters' in Pr
mm.000
(alternatively enter a value of 1000
in Pr
mm.000
) and press red reset button or toggle the reset
digital input.
Run Drive is now ready to run
Action Detail