Powerdrive F300 Getting Started Guide 79
Issue Number: 5
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Basic parameters
(Menu 0)
Running the
motor
Optimization
NV Media Card
Operation
Further
information
UL listing
information
Table 7-9 Dyneo LSRPM 5500 rpm motors
* From firmware version 01.12.xx.xx onwards, the rated current from the motor nameplate is entered
into Pr 05.007 / Pr 00.046 and will be updated automatically to the sensorless value after an
autotune.
LSRPM Motor model
Motor rated
current
(nameplate
value)
Pr 00.046
*
Sensorless
motor rated
current after
autotune
*
Switching
frequency
Pr 00.041
Ke
Pr 00.047
Motor
Thermal
Time
Constant
Pr 00.053
A A kHz V/1000 rpm s
5500 LSRPM 132M 18.6 kW 35.0 35.0 8 74 1050
5500 LSRPM 132M 23 kW 44.0 44.0 8 74 1050
5500 LSRPM 132M 27 kW 52.0 52.0 8 77 1050
5500 LSRPM 160MP 35 kW 67.0 67.0 8 76 1050
5500 LSRPM 160MP 44 kW 82.0 82.0 8 77 1050
5500 LSRPM 160LR 52 kW 97.0 97.0 8 77 1050
5500 LSRPM 200L1 70 kW 140 141 8 68 900
5500 LSRPM 200L1 85 kW 170 170 8 64 900
5500 LSRPM 200L1 100 kW 210 210 8 64 900
5500 LSRPM 200L2 140 kW 265 296 8 67 900
Powerdrive F300 Getting Started Guide English Iss2.book Page 79 Tuesday, July 28, 2015 3:23 PM