Installation and Configuration
Analog output configuration in TankMaster
To configure the Rosemount 2410 Tank Hub analog output:
1. In the WinSetup workspace click the right mouse button on the tank hub icon and
choose the Properties option.
2. Select the Configuration tab.
3. Click the Analog Output button to open the Analog Output Configuration
window
(1)
.
4. Check the Enable box to activate the analog output option.
5. Configure Source Parameter, Value Range, and Alarm Mode. See Appendix C in the
Rosemount 2410 Tank Hub Reference Manual
(2)
for more information on how to
configure the analog output.
Note
In case a Proof Test Reference Reflector is used, make sure that the Value at 20 mA is set
above the position of the reflector.
1. Note that this button is available if the Analog Output option is activated for the Rosemount 2410 Tank Hub.
2. Document No 00809-0100-2410