12
Safety Manual
00809-0400-5100, Rev AB
Installation and Configuration
November 2019
Installation and Configuration
2.4 Write protection
A Rosemount Tank Gauging safety-certified system should always be write protected in
order to avoid unintentional configuration changes. The Rosemount 5900 Radar Level
Gauge as well as the Rosemount 2410 Tank Hub should be write protected.
It is recommended to use one of the following write protection options:
Hardware switch
Software password protected function
See the appropriate reference manuals listed in “Installation in SIS applications” on page 8
for more information on how to enable write protection.
2.5 Site acceptance
After installation and/or configuration, proper operation of the transmitter (including
verification of all configuration changes) must be verified. A site acceptance test is therefore
required. The proof test outlined in this document can be used for this.