2.3.2 Relay configuration
To configure Rosemount 2410 Tank Hub relays:
1. In the WinSetup workspace click the right mouse button on the tank hub icon,
choose Properties and select the Configuration tab.
2. Click one of the Virtual Relay No. buttons. See Appendix C in the Rosemount 2410
Tank Hub Reference Manual
(1)
for more information on how to configure relays.
Normally Open/Normally Closed
Normally Open (NO) is the default setting for the Rosemount 5900 and Rosemount 2410 in
Safety Instrumented Systems (SIS). Verify the relay configuration by, for example, using the
proof test function Relays K1/K2 Verification Test. See “Maintenance” on page 29 for more
information.
See the Rosemount 2410 Tank Hub Reference Manual
(1)
for more information on the
Rosemount 2410 relays.
Note
In case a Proof Test Reference Reflector is used, make sure that the relay set point is set
below the position of the reflector.