3.5.4 Relay output verification
This proof test verifies the relay output, i.e. whether the relay is able to open and close.
The relay output may be verified by using a multimeter or the SIF logic solver (Safety PLC) to
ensure that relay output from the Rosemount 2410 corresponds to indicated relay state in
TankMaster.
To run a relay output verification test do the following:
1. Ensure that the TankMaster WinSetup program is up and running. Open the Proof
Test window and select the Relays K1/K2 check box (see “Maintenance” on
page 29).
2. Click the Start Guided Proof Test button and follow the instructions in the Guided
Proof Test wizard:
a. Verify that K1 relay output corresponds to the presented relay state.
b. Manually change relay state and verify that relay state changed and corresponds to
the presented state for K1.
c. Verify that K2 relay output corresponds to the presented relay state.
d. Manually change relay state and verify that relay state changed and corresponds to
the presented state for K2.
3.5.5 Analog output verification
This test verifies that the 4-20 mA analog output responds to level measurement failure by
switching to the configured alarm mode. See “Analog output configuration” on page 9 for
more information on how to configure the Analog Output.
The analog output may be verified by using a multimeter or the SIF logic solver (Safety PLC)
to measure and verify that the analog output current value from the Rosemount 2410
corresponds to the current value indicated in Rosemount TankMaster. The test includes
verification of output current, High Alarm current, and Low Alarm current.
To run an Analog Output Verification test do the following:
1. Ensure that the TankMaster WinSetup program is up and running. Open the Proof
Test window and select the Analog Output check box (see “Maintenance” on
page 29).
2. Click the Start Guided Proof Test button and follow the instructions in the Guided
Proof Test wizard:
a. Verify the output current value from the Rosemount 2410 Tank Hub.
b. Verify the High alarm current value from the Rosemount 2410 Tank Hub.
c. Verify the Low alarm current value from the Rosemount 2410 Tank Hub.