21
Safety Manual
00809-0400-5100, Rev AB
Operation and Maintenance
November 2019
Operation and Maintenance
10. Note the Warning that appears when starting the Proof Test:
Note
Ensure that the necessary actions are taken in order to maintain safety during the test.
11. Click the Accept button to run the test. Now the gauge will measure the actual
distance to the reference reflector.
12. Verify that the safety loop is set to alarm state during the proof test.
13. Once a successful High Level Alarm proof test is finished, it will be confirmed. Now
the gauge will return to normal operation.
14. After the High Level Alarm test is finished, click the Next button to proceed with
the appropriate output verification test.