Quick Start Guide
11
March 2018
Pressure example
DP Flow example
DP Level example
To display pressure on the LCD meter
With option code IT6, select the “Pressure” check box on the display
configuration screen.
Note
To display level or flow, use AI block out.
Parameters Enter data
Channel 1
L_Type Direct
XD_Scale See list of supported engineering units.
Out_Scale Set values outside operating range.
Parameters Enter data
Channel 1
L_Type Square root
XD_Scale 0–100 inH
2
O @ 68 °F
Out_Scale 0–20 GPM
Parameters Enter data
Channel 1
L_Type Indirect
XD_Scale 0–300 inH
2
O @ 68 °F
Out_Scale 0–25 ft
Parameters Enter data
Display parameter 1
Block type #1 Sensor transducer block
Block tag Transducer
Param index Primary variable
Units type Auto