Quick Start Guide
Note
The device description loaded in the host system must be at the same revision as this
device. The device description can be downloaded from Emerson.com/Rosemount
or
Fieldbus.org.
3.0 Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. First, rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing
counter clockwise to the desired location (up to 360° from thread limit).
3. Retighten the housing rotation set screw.
Figure 5. Transmitter Housing Set Screw
A. Housing rotation set screw (
3
/32-in.)
4.0 Connect wiring and power up
4.1 Cable connection
The segment cable can enter the transmitter through either conduit
connection on the housing. Cable entering the housing vertically should be
avoided. Drip loops are recommended for installations where moisture can
accumulate and enter the terminal compartment.
4.2 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 17.5 Vdc for FISCO) at
the terminals to operate and provide complete functionality.
4.3 Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.