Quick Start Guide
15
March 2018
7.6 Europe
E1 ATEX Flameproof
Certificate: KEMA 00ATEX2143X
Standards: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015
Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(–60 °C T
a
+70 °C),
T5/T4(–60 °C T
a
+80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a
boundary between EPL Ga (process connection) and EPL Gb (all other parts of the
equipment). The model code and data sheet are to be consulted for details of the
diaphragm material. Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected. The
manufacturer's instructions for installation and maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth. If paint is ordered through a special
option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C
greater than maximum specified temperature for location where installed.
I1 ATEX Intrinsic Safety
Certificate: BAS01ATEX1303X
Standards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012
Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C T
a
+70 °C)
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This
must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree
of protection of at least IP20 in accordance with IEC/EN 60529.
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Model U
i
I
i
P
i
C
i
L
i
SuperModule
30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 μH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH
3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 μH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A