92
Reference Manual
00809-0200-4702, Rev CA
Section 9: Operation and Maintenance: Models 702DX32 and 702DX42
February 2013
Operation and Maintenance: Models
702DX32 and 702DX42
Figure 9-8. Output Circuit Wiring
Figure 9-9. Possible Configurations for Both Channel 1 and Channel 2
Discrete output switch voltage and current limits
It is important to note that the maximum output switching capacity is 26 volts DC and 100
milliamps. If a greater is to be switched an interposing relay circuit can be used. Figure 9-9 shows
an example of a circuit to switch higher currents or voltages.
Special considerations for dual output circuits:
If both channels are connected to output circuits, it is very important that the CMN terminal of
each circuit be at the same voltage. Employing a common ground for both output circuits is one
way to ensure that both circuits have CMN terminals at the same voltage.