95
Reference Manual
00809-0200-4702, Rev CA
Section 9: Operation and Maintenance: Models 702DX32 and 702DX42
February 2013
Operation and Maintenance: Models 702DX32 and
702DX42
Table 9-4. State table for Discrete Output
Note
The Fault condition applies to all Reported Value settings.
Changing logic option from Direct to Inverted has the effect of changing “Open Switch” to
“Closed Switch” on the table above.
The Manual Override of an output channel changes the value from the “Open Switch” state to
the “Closed Switch” state.
State Table for Channels Set to Output Direction
Value Name Analog Value Discrete Value
Reported Value
Open
Switch
Closed
Switch
Open
Switch
Closed
Switch
Open
Switch
Closed
Switch
Default False True 0.000 1.000 240 242
Off/On Off On 0.000 1.000 0 1
Opened/Closed Opened Closed 46.000 6.000 46 6
Running/Stopped Stopped Running 25.000 26.000 25 26
Slow/Fast Slow Fast 8.000 7.000 8 7
Forward/Reverse Forward Reverse 9.000 10.000 9 10
Bottom/Top Bottom Top 12.000 11.000 12 11
Empty/Full Empty Full 14.000 13.000 14 13
Cold/Hot Cold Hot 16.000 15.000 16 15
Dry/Wet Dry Wet 32.000 33.000 32 33
Absent/Present Absent Present 45.000 44.000 45 44
Fault Fault 243.000 243