23
Reference Manual
00809-0200-4702, Rev CA
Section 3: Mounting, Wiring Switches, and Sensors:
Models 702DX22 and 702DX61
February 2013
Mounting, Wiring Switches, and Sensors:
Models 702DX22 and 702DX61
Dual Input, Limit Contact Logic
When configured for Limit Contact Logic, the 702 transmitter will accept the input from two
single pole single throw switches on inputs S1 and S2, and will use limit contact logic for the
determination of the wireless outputs. Please reference Figure 3-7 for details on the wireless
outputs available when using limit contact logic.
Figure 3-7. Dual Input, Limit Contacts
Dual Input, Opposing Contact Logic
When configured for Opposing Contact Logic, the 702 transmitter will accept the input from a
single pole double throw switch on inputs S1 and S2, and will use opposing contact logic for the
determination of the wireless outputs. Please reference Figure 3-8 for details on the wireless
outputs available when using opposing contact logic.
Figure 3-8. Dual Input, Opposing Contact
Dual Input
Limit Contacts
S1
CMN
S2
CMN
Dual Input
Opposing Contact
S1
CMN
S2
CMN