2.3.5 Mating pipe ID (Inside Diameter)
The Pipe ID (Inside Diameter) of the pipe adjacent to the flowmeter can cause entrance
effects that may alter flowmeter readings. You must specify the exact inside diameter of
the pipe to correct for these effects. Enter the appropriate value for this variable.
Pipe ID values for schedule 10, 40, and 80 piping are given in Table 2-1. If the piping in your
application is not one of these, you may need to contact the manufacturer for exact Pipe ID.
f
2.3.6 Variable mapping
Allows the user to select which variables the Rosemount 8600D will output.
Primary Variable (PV)
Selections for this Variable are Mass Flow, Volumetric Flow, Velocity Flow, and Process
Temperature. The Primary Variable is the variable mapped to the analog output.
Secondary Variable (SV)
Selections for this Variable include all Variables that can be mapped to PV, and also Vortex
Frequency, Pulse Output Frequency, Totalizer Value, Calculated Process Density,
Electronics Temperature, and Cold Junction (CJ) Temperature.
Tertiary Variable (TV)
Selections for this Variable are identical to those of the Secondary Variable.
Quaternary Variable (4V)
Selections for this Variable are identical to those of the Secondary Variable.
FastKeys
1, 3, 5
Table 2-1. Pipe IDs for Schedule 10, 40, and 80 Piping
Pipe Size
Inches (mm)
Schedule 10
Inches (mm)
Schedule 40
Inches (mm)
Schedule 80
Inches (mm)
1 (25) 1.097 (27.86) 1.049 (26.64) 0.957 (24.31)
1? (40) 1.682 (42.72) 1.610 (40.89) 1.500 (38.10)
2 (50) 2.157 (54.79) 2.067 (52.50) 1.939 (49.25)
3 (80) 3.260 (82.80) 3.068 (77.93) 2.900 (73.66)
4 (100) 4.260 (108.2) 4.026 (102.3) 3.826 (97.18)
6 (150) 6.357 (161.5) 6.065 (154.1) 5.716 (145.2)
8 (200) 8.329 (211.6) 7.981 (202.7) 7.625 (193.7)
FastKeys
1, 3, 6
FastKeys
1, 3, 6, 1
FastKeys
1, 3, 6, 2
FastKeys
1, 3, 6, 3
FastKeys
1, 3, 6, 4