Rosemount 8600 Vortex Flow Meter
Damping
Changes the response time of the flowmeter to smooth variations in output readings
caused by rapid changes in input.
The appropriate damping setting can be determined based on the necessary response
time, signal stability, and other requirements of the loop dynamics in your system.
PV damping
The default damping value is 2.0 seconds. Damping can be reset to any value between 0.2
and 255 seconds when PV is a flow variable or 0.4 to 32 seconds when PV is Process
Temperature.
Flow damping
The default damping value is 2.0 seconds. Flow Damping can be reset to any value between
0.2 and 255 seconds.
Temperature damping
The default damping value is 2.0 seconds. Temperature Damping can be reset to any value
between 0.4 and 32 seconds.
LFC response
Defines how the output of the Vortex meter will behave entering into and coming out of
the Low Flow Cutoff. Options are stepped or damped. (See Technical Note
00840-0200-4004 for more information regarding Low Flow Measurement).
4.3.4 Device information
Information variables are used for identification of flowmeters in the field and to store
information that may be useful in service situations. Information variables have no effect on
flowmeter output or process variables.
Manufacturer
An informational variable provided by the factory. For the Rosemount 8600D, the
Manufacturer is Rosemount.
FastKeys
1, 4, 3, 4
FastKeys
1, 4, 3, 4, 1
FastKeys
1, 4, 3, 4, 2
FastKeys
1, 4, 3, 4, 3
FastKeys
1, 4, 3, 5
FastKeys
1, 4, 4
FastKeys
1, 4, 4, 1