Reference Manual
00809-0100-4860, Rev BF
Troubleshooting
May 2019
74
Rosemount 8600 Vortex Flow Meter
5.6.1 Replacing the terminal block in the housing
To replace the Field Terminal Block in the housing, you will need a small screwdriver. Use
the following procedure to replace the terminal block in the housing of the Rosemount
8600D.
Note
Remove power before removing the electronics cover.
Remove the terminal block
1. Turn off the power to the Rosemount 8600D.
2. Unscrew the cover.
A. Cover
B. O-ring
C. Terminal block
D. Captive screws (3x)
3. Disconnect the wires from the field terminals. Be sure to secure them out of the
way.
4. Remove the ground screw if transient protection (Option T1) is installed.
5. Loosen the three captive screws.
6. Pull outward on the terminal block to remove it from the housing.
Figure 5-6. Terminal Block Assembly
See Safety Messages on page 65 for complete warning
C
B
D
A