87
Rosemount 8600 Vortex Flow Meter
Reference Manual
May 2019
Specifications and Reference Data
00809-0100-4860, Rev BF
Appendix A Specifications and Reference
Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 95
Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 96
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 97
A.1 Specifications
The following specifications are for the Rosemount 8600D
except where noted.
A.2 Functional specifications
Process fluids
Liquid, gas, and steam applications. Fluids must be
homogeneous and single-phase.
Line sizes
Flanged style
1, 1
1
/2, 2, 3, 4, 6, and 8 inches
(DN 25, 40, 50, 80, 100, 150, and 200)
Pipe schedules
Process piping Schedules 10, 40, 80, and 160.
Note
The appropriate bore diameter of the process piping
must be entered using the Field Communicator or
AMS Device Manager. Meters will be shipped from
the factory at the Schedule 40 default value unless
otherwise specified.
Measurable flow rates
Capable of processing signals from flow applications which
meet the sizing requirements below.
To determine the appropriate flowmeter size for an
application, process conditions must be within the
Reynolds number and velocity limitations for the desired
line size provided in Table A-1, Table A-2, and Table A-3.
Note
Consult your local sales representative to obtain a
computer sizing program that describes in greater
detail how to specify the correct flowmeter size for an
application.
The Reynolds number equation shown below combines the
effects of density (r), viscosity (m
cp
), pipe inside diameter
(D), and flow velocity (V).
Table A-1. Minimum Measurable Meter Reynolds
Numbers
Meter Sizes
(Inches / DN)
Reynolds Number
Limitations
1 through 4/25 through 100
5000 minimum
6 through 8/150 through
200
Table A-2. Minimum Measurable Meter
Velocities
(1)
1. Velocities are referenced to schedule 40 pipe.
Feet per Second
Meters per
Second
Liquids
Gases
The is the process fluid density at flowing conditions in
lb/ft
3
for ft/s and kg/m
3
for m/s
R
D
VD
cp
------------=
36/
54/
36/
54/