ER5000 —
214
Troubleshooting
Operation
Checking the Pressure Connections if the ER5000 Does Not
Respond Properly to Setpoint Changes (cont.)
5. Make sure that a Control Limit has not been triggered. Refer
to The Control Limits Panel for more information.
6. If the problem persists, use The Plot Screen Buttons — The
Print Button to take a snapshot of your current conguration
and gather all tuning parameters, then contact your
TESCOM™ representative.