Unidrive M600 Getting Started Guide 59
Issue Number: 2
Safety information Product information
Mechanical
installation
Electrical installation Getting started Basic parameters
Running the motor
NV Media Card
Operation
Further information
7.2 Quick Start / start-up
7.2.1 Open loop
Action Detail
Before
power-up
Ensure:
• The drive enable signal is not given (terminal 31)
• Run signal is not given
• Motor is connected
Power-up the
drive
Verify that Open Loop mode is displayed as the drive powers
up. If the mode is incorrect see
section 5.6 Changing the
operating mode
on page 43 .
Ensure that the drive displays ‘Inhibit’
Enter motor
nameplate
details
Enter:
• Motor rated frequency in Pr 00.047 (Hz)
• Motor rated current in Pr 00.046 (A)
• Motor rated speed in Pr 00.045 (rpm)
• Motor rated voltage in Pr 00.044 (V) - check if or
connection
Set maximum
frequency
Enter:
• Maximum frequency in Pr 00.002 (Hz)
Set
acceleration /
deceleration
rates
Enter:
• Acceleration rate in Pr 00.003 (s/100 Hz)
• Deceleration rate in Pr 00.004 (s/100 Hz) (If braking resistor
installed, set Pr 00.015 = Fast. Also ensure Pr 10.030 and
Pr 10.031 and Pr 10.061 are set correctly, otherwise
premature ‘Brake R Too Hot’ trips may be seen).
Motor
thermistor
set-up
The motor thermistor can be selected in Pr 07.015. Refer to
Pr 07.015 for further information.
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
VHzmin
-1
kW cos
φ
A
230
400
50 1445 2.20 0.80 8.50
4.90
CN = 14.5Nm
240
415
50 1445 2.20 0.76 8.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,4 6A P=110W R.F 32MN
I.E.C 34 1(87)
Unidrive M600 Getting Started Guide English Iss1.book Page 59 Friday, April 25, 2014 2:08 PM