34 Unidrive M600 Getting Started Guide
Issue Number: 2
4.4 Ground connections
The drive must be connected to the system ground of the AC supply. The ground wiring must
conform to local regulations and codes of practice.
On size 3 and 4, the supply and motor ground connections are made using the M4 studs located
either side of the drive near the plug-in power connectors. See Figure 4-1 and Figure 4-2 for details.
On size 5, the supply and motor ground connections are made using the M5 studs located near the
plug-in power connector. Refer to Figure 4-3.
On a size 6, the supply and motor ground connections are made using the M6 studs located above
the supply and motor terminals. Refer to Figure 4-4.
On size 7, the supply and motor ground connections are made using the M8 studs located by the
supply and motor connection terminals. Refer to Figure 4-5.
On size 8, the supply and motor ground connections are made using the M10 studs located by the
supply and motor connection terminals. Refer to Figure 4-5.
On size 9E and 10, the supply and motor ground connections are made using the M10 studs located
by the supply and motor connection terminals. Refer to Figure 4-6.
Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against corrosion i.e. as could be caused
by condensation.
For further information on ground cable sizes, refer to Table 2-6 Protective ground cable
ratings on page 11.
The ground loop impedance must conform to the requirements of local safety regulations.
The drive must be grounded by a connection capable of carrying the prospective fault
current until the protective device (fuse, etc.) disconnects the AC supply.
The ground connections must be inspected and tested at appropriate intervals.