2.7 Electrical Data
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage- Phase
208/230-1 208/230-3 460-3 575-3
14 1
FLA 9.1
WSA 11.0
OPD 15
20 1.5
FLA 12.1
WSA 14.8
OPD 25
27 2
FLA 13.4
WSA 16.4
OPD 25
37 3
FLA 18.5 13.4 7.1 5.8
WSA 22.8 16.4 8.7 7.0
OPD 35 25 15 15
42 3.5
FLA 15.0 7.1 6.0
WSA 18.4 8.7 7.2
OPD 30 15 15
67 5
FLA 24.1 11.7 9.1
WSA 29.3 14.2 11.1
OPD 45 20 15
96 8
FLA 36.2 18.1 13.4
WSA 41.4 20.6 15.3
OPD 60 30 20
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Table 2.16 Electrical data—Standard sound and ambient models (95°F/35°C)