Use the following procedure to log in to the Gateway:
Procedure
1. Open a standard web browser.
2. Enter https://192.168.1.10 in the address bar.
3. Continue though the security message.
4. Enter admin for User Name.
5. Enter default for the Password.
The web browser will now be directed to the Gateway’s default home page. There is
a navigation menu located on the left hand side with four main areas.
• Diagnostics: View status of communications, client server parameters, and more
• Monitor: Screens created by the user to view data from field devices
• Explorer: Basic view of values from field devices
• Setup: Configure the Gateway for operations, security, and host system
integration
Security passwords
There are four role-based user accounts for the Gateway with varying levels of access.
Table 2-2 describes this access.
Table 2-2: Role Based Access User Accounts
Role User name Web Interface Access
Executive exec Read-only access
Operator oper Read-only access
Maintenance maint Configure HART
®
device settings
Configure Modbus communications
Configure Modbus register mapping
Configure OPC browse tree
Configure Active Advertising
Administrator admin Includes all maintenance privileges
Configure Ethernet network settings
Configure WirelessHART
®
network settings
Set passwords
Set time settings
Set home page options
Configure custom point pages
Restart applications
Each of the initial passwords for the user accounts is default. It is recommended, for
security purposes, that these passwords are changed. The administrator password should
be appropriately noted when changed. If it is lost, do not return the Gateway to the
factory, see Resetting to factory defaults.
Configuration Reference Manual
September 2020 00809-0200-4410
10 Emerson.com/Rosemount