1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009 XC1008-1011-1015D 25/66
C8 = FAn1;
C9 = FAn1;
C10 = FAn1;
C11 = FAn1;
C12 = nu
C13 = nu
C14 = nu
C15 = nu
PLANT CONFIGURATION EXAMPLE:
Plant with 1 circuit with 6 compressors e 5 fans:
C0 = 1A1d;
C1 = CPr1;
C2 = CPr1;
C3 = CPr1,
C4 = CPr1,
C5 = CPr1;
C6 = CPr1;
C7 = FAn1;
C8 = FAn1;
C9 = FAn1;
C10 = FAn1;
C11 = FAn1;
C12 = nu
C13 = nu
C14 = nu
C15 = nu
Plant with 1 circuit with 3 compressors, 2 of them without valves, and 1
compressor with 2 valves e 4 fans:
C0 = 1A1d;
C1 = CPr1;
C2 = CPr1;
C3 = CPr1,
C4 = Stp,
C5 = Stp;
C6 = FAn1;
C7 = FAn1;
C8 = FAn1;
C9 = FAn1;
C10 = nu
C11 = nu
C12 = nu
C13 = nu
C14 = nu
C15 = nu
Plant with 2 suctions and 2 deliveries:
Suction 1: 1frequency compressor, 1 compressor without valves and 1 compressors with
2 valves
Delivery 1: 3 fans
Suction 2: 1frequency compressor, 2 compressors
Delivery 2: 1 inverter fan, 2 fans
C0 = 2A2d;