56 • XM678D I&O Manual 026-1219 Rev 3
CoM tEn
Modulating output
configuration
PM
5; PM6; OA7; CUr;
tEn
For models with PWM/ O.C. output:
PM5 = PW
M 50Hz
PM6 = PWM 60Hz
OA7 = two state, it can be used as an
op
en collector output.
For models with [4 to 20mA] or
[0 to 10V] output:
Cur = 4 to
20mA current output.
tEn
= 0 to 10V voltage output.
AOP CL
Alarm relay
p
olarity
OP
; CL
CL = normally closed
OP = normally open
ed
iAU n
Auxiliary output
indepe
ndent from
ON/OFF state
n; Y
n = if
the instrument is switched off also
the au
xiliary output is switched off.
Y = the auxi
liary output state is
un
related to the ON/OFF device status.
DIGITAL INPUTS
i1P CL
Digital input 1
polarity
OP
; CL
CL = t
he digital input is activated by
closing the contact.
OP = t
h
e digital input is activated by
openin
g the contact.
i1F dor
Digital input 1
configuration
EAL; bAL
; PAL; dor;
dEF
; A
US; LiG; OnF;
Htr; FHU; ES; HdY
EAL = external alarm; bAL = seri
ous
external alarm; PAL = pressure switch
activation; dor = door open;
dEF = defrost acti
vati
on;
AUS = auxiliary activation;
LiG = light activation;
OnF = swit
ch on/off the instrument;
Htr = ch
ange type of action;
FHU = no
t used; ES = activate en
ergy
saving; HdY = activate holiday
function
d1d 15
Digital input 1
activation
delay
0 to 255min
When [i1F = PAL]:
time interval to
calculate the number of the pressure
switch activation.
When [i1F
= EAL or bAL] (external
alarms): d1d parame
ter defines the time
delay between the detection and the
successive signaling of the alarm.
When [i1F
= dor]: this i
s the delay to
activate door open alarm.
i2P CL
Digital input 2
polarity
OP
; CL
CL = the di
gital input is activated by
closing the contact.
OP = t
h
e digital input is activated by
openin
g the contact.
Label Value Description Range Notes
Table 24-1 - Default Parameter Map