WLCG/WLHG
High-Wall Air Handlers
• Installation, Operation and Maintenance Manual •
P/N 240008111, Rev. G [06/18/10] 27
Unit-Mounted Controller Operation (continued)
(Heat source ON, heat pump ON). See (Fig-
ure 28, Page 22).
For heat pump operation with backup electric
heat, rst turn the unit on via the ON/OFF
buon.
Select Heat mode via the Mode buon.•
e room temperature and setpoint tem-•
perature will be displayed.
Press either the Up or Down arrow but-•
tons to change the setpoint temperature.
e setpoint temperature will change by •
one degree with each successive press of
the Up or Down arrow buons. Holding
the buon in will change the temperature
rapidly.
Place the setpoint temperature above the
room temperature by one degree.
e compressor will start and heating will •
continue for a minimum of two minutes
and as long as the setpoint remains above
room temperature.
When the room temperature has been •
satised for at least 60 seconds and the
minimum on time has elapsed, the com-
pressor will switch o.
e fan will operate as described in Fan •
operation, page 25.
Place the setpoint temperature above the
room temperature by at least two degrees.
e compressor will start and, the electric •
heat will also energize aer a 30 second
delay, thus two-stage heating.
e electric heat will run for a minimum •
of two minutes and until the deviation
between room temperature and setpoint
temperature is less than two degrees.
At that time the electric heat will switch •
o and the heat pump (compressor) will
take over the heating demand.
e electric heater will not re-start until a •
three minute delay has elapsed.
Once the room temperature is satised •
and the two-minute minimum run time
has elapsed, the compressor will cycle
o.
e compressor will not re-start until a •
three minute delay has elapsed.
e fan will operate as described in Fan •
operation, page 25.
DRY mode
For Dry mode operation the unit must have
an electric heater. Also the control must rst
be congured properly (Heat source ON).
See (Figure 28, Page 22).
Dry mode will remove humidity from the air
while maintaining setpoint temperature.
is is done by energizing the compressor •
in cooling along with the electric heater.
Dry mode will not maintain a specic •
humidity level.
e unit must be equipped with an op-•
tional electric heat element.
For Dry Mode operation, rst turn the unit
on via the ON/OFF buon.
Select Dry mode via the MODE buon.•
e room temperature and setpoint tem-•
perature will be displayed.
Press either the Up or Down arrow but-•
tons to change the setpoint temperature.
e setpoint temperature will change by •
one degree with each successive press of
the Up or Down arrow buons. Holding
the buon in will change the temperature
rapidly.
Place the setpoint temperature at a desired
room temperature.
Depending on the difference between •
room temperature and setpoint tempera-
ture the compressor and/or heat source
will energize.
If the room temperature and setpoint •
temperature are the same the compressor
will operate in cooling and the electric
heat will also energize.
Should the room temperature fall below •
the setpoint temperature by two degrees,
the compressor will stop and heating will